EasyManua.ls Logo

GE Security Vigilant VS2 - Control panel testing

GE Security Vigilant VS2
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4: Reports
Vigilant VS1 and VS2 Technical Reference Manual 171
To view a Device Maintenance report:
1. Press the menu button and choose Reports.
2. Choose Device Maintenance.
3. Choose one of the following:
All Devices
Devices >= 20% Dirty
Devices >= 80% Dirty.
Main Menu
Reports
Test
Control
Program
Reports
Device Maintenance
System Status
Correlation Groups
Device Maintenance
All Devices
Devices >= 20%
Dirty
Devices >= 80%
Dirty
System Status report
The panel provides a System Status report for all active points in the system. The
report can include: all active points, all alarm points, all supervisory points, all trouble
points, all disabled points, or all other points. System status reports can be printed or
viewed on the LCD.
To view a System Status report:
1. Press the menu button and choose Reports.
2. Choose System Status.
3. Choose one of the following:
All
Alarm
Supervisory
Trouble
Disable
Other
Main Menu
Reports
Test
Control
Program
Reports
Device Maintenance
System Status
Correlation Groups
Corr Group Config
System Status
All
Alarm
Supervisory

Table of Contents

Related product manuals