Chapter 5: Diagnostics, maintenance, and testing
Vigilant VS1 and VS2 Technical Reference Manual 185
message is sent to both lines regardless of the success of the transmission for either
account.
Note: Before conducting a test, configure the dialer’s accounts for proper operation.
To conduct a dialer test:
1. Press the control panel’s Menu button.
2. Choose Test.
3. Choose Dialer.
4. Enter a level one password.
5. Select the account that you want to test.
6. Press Enter.
Note: The test message is sent to the CMS account
that you selected. For verification of the CMS account
receiving the test message, you must be in contact
with the CMS account during the test. Nothing is
displayed on the LCD.
7. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Main Menu
Reports
Test
Control
Program
Test
Walk Test Audible
Test Fire
Dialer
Enter Password
0000
Dialer
Account 1
Account 2
Conducting a lamp test
A lamp test lights all of the LEDs on the panel and the LED annunciator and tests the
LCD so that you can verify proper operation. LEDs stay on for 15 seconds.
To conduct a lamp test:
1. Press the menu button and choose Test.
2. Choose Lamp Test.
3. Press Enter.
4. Verify that all LEDs on the panel, the LCD, and the
LED annunciator (if used) work properly.
Main Menu
Reports
Test
Control
Program
Test
Test Fire
Dialer
Lamp Test

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals