Chapter 2: Front panel programming
Vigilant VS1 and VS2 Technical Reference Manual 31
UL 864 programming requirements
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
certain programming features or options must be limited to specific values or not used at all as
indicated below.
Programmable
feature or option
Permitted in
UL 864? (Y/N)
Possible settings Settings
permitted in UL
864
Panel default
AC fail delay Y 0 to 15 hours 1 to 3 hours 3 hours
Telephone line cut
supervision duration
Y 1 to 120 seconds 10 to 120
seconds
120 seconds
Test signal
frequency
Y 0 to 45 days 1 (daily) 1 (daily)
Dialer mode Y Dual line
Single line
Modem only
None
Dual line
Single line [1]
Modem only [2]
None [2]
Dual line
Send event restore
codes
Y No
Yes
Yes Yes
Swinger shutdown N Off
1 to 255
Off Off
Zone resound Y On
Off
On On
[1] Allowed only when the supervising station supervises the telephone line and annunciates fault
conditions within 200 seconds
[2] Prohibited when the control panel is connected to a supervising station

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals