Chapter 3: System operation
Vigilant VS1 and VS2 Technical Reference Manual 155
To activate or restore an output device:
1. Press the menu button and choose Control.
2. Enter a level one password.
3. Choose Activate/Restore.
4. Choose Device.
5. Choose the loop the device is on.
Note: If the panel only has one loop, the loop
selection screen does not display. Go to the next
step.
6. Enter the device ID for the device that you want to
activate or restore.
7. Press Enter.
8. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Main Menu
Reports
Test
Control
Program
⇩
Enter Password
0000
⇩
Control
Enable/Disable
Activate/Restore
⇩
Activate/Restore
Device
Panel NAC
⇩
Device
Loop 01<>
⇩
Device Activate<>
001
Device 001
Unlatching latched output devices
Latched outputs are devices that are configured to shut down air handlers and
dampers automatically when an alarm activates, and to keep them shut down until
they are manually unlatched and restored. For this reason, devices configured as
latched output devices must be manually unlatched and then restored.
When outputs are latched, the panel generates an “Outputs are latched” event. The
unlatch command affects all latched output devices system-wide. You can assign the
Unlatch Outputs command to a programmable key on the front panel or to a Class A
or B Signature input module circuit with one of the devices listed on page 96.
To unlatch latched output devices:
1. Press the Unlatch Outputs button on the control panel (if programmed).
— or —
Press the Unlatch Outputs module button (if programmed).