Chapter 2: Front panel programming
Vigilant VS1 and VS2 Technical Reference Manual 79
To change loop configuration options:
1. Press the menu button and choose Program.
2. Choose Advanced Program.
3. Enter a level two password.
4. Choose Loop Configuration.
5. Program the options.
Main Menu
Reports
Test
Control
Program
Program
Incremental Program
Auto Program
Advanced Program
Enter Password
0000
Advanced Program
Loop Configuration
Panel Configuration
Panel Operation
Correlation group programming
This section includes instructions for:
Using fast groups
Adding members to correlation groups
Enabling in-suite signal silence
Setting the activation count
Copying members of a correlation group
Removing all members from a correlation group
Note: To meet the UL\ULC requirement that evacuation signals activate within 10
seconds, assign sounder base detectors to “fast” correlation groups.
See “Programming fast groups for sounder bases” on page 85.
If you are new to correlation group programming, see “What is a zone?” on page 32.
Adding members to correlation groups
Correlation groups can include zones, NACs, devices, unconfigured alarm events, and
the common trouble event. See the following procedure.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals