Chapter 3: System operation
142 Vigilant VS1 and VS2 Technical Reference Manual
Programmable button function priority
Operations such as Signal Silence, Auto Signal Silence, and Drill take priority over
Activate, Restore, and Disable.
Activate, Restore, and Disable take priority over In Suite Signal Silence.
A single Restore or Disable takes priority over one or more Activates.
Restore or Group Disable only affect devices from correlation groups that have
been added to the list for that button.
Although an Activate button can turn on both latched and unlatched devices, it
can only turn off unlatched devices. Latched outputs remain active until you press
a button programmed for Unlatch. Until the output has been unlatched, the panel
displays an “Outputs are Latched” monitor event message.
The Disable and Restore commands do not affect active latched outputs until
after the Unlatch button has been pressed. Until the output has been unlatched,
the panel displays an “Outputs are Latched” monitor event message.