Chapter 2: Front panel programming
58 Vigilant VS1 and VS2 Technical Reference Manual
Option Description
Label devices Configures the auto programming sequence to allow you to label devices
using the alphanumeric keypad.
Yes: Enables device labeling
No: Disables device labeling
Label zones Configures the auto programming sequence to allow you to label zones using
the alphanumeric keypad.
Yes: Enables zone labeling
No: Disables zone labeling
Follow This option controls the conditions that will activate relay or sounder detector
bases. Select from the following values:
Head: The base is controlled by the detector’s settings.
• The base activates when the detector goes into alarm, unless the
detector is set for alarm verification.
• If the detector is set for alarm verification, the base activates when the
detector goes into alarm verification. It does not restore, however, until
the alarm restores.
• The base does not respond when the detector goes into prealarm no
matter how the detector is configured.
• Devices with the base set to follow “Head” cannot be placed in
correlation groups. When a device base is set to follow "Head," the base is
removed as an output from any Correlation Groups to which it belongs.
Alarm: The base activates its relay when the detector goes into alarm. The
base will not restore until the alarm event has been restored.
Alarm and verify (ALM+VFY): The base activates its relay when the detector
goes into alarm verify and continues when the detector goes into alarm. The
base will not restore until both events have been restored.
Alarm and prealarm (ALM+PALM): The base activates its relay when the
detector goes into prealarm and continues when the detector goes into an
alarm. The base will not restore until both events have been restored.
Riser: The base is triggered individually by the loop controller (sounder bases
only)
None: A correlation group triggers the base. It can be applied to both relay
and sounder bases and is used for relay bases configured as latched output
devices.
Note: All base follow settings except “Head” and “Riser” can be activated by
correlation groups.