Chapter 5: Diagnostics, maintenance, and testing
Vigilant VS1 and VS2 Technical Reference Manual 187
• Input zones programmed as waterflow with retard require 10 to 15 seconds of
activation to initiate the test signals.
• Devices programmed as alarm verify and not in test mode go directly into alarm if
activated (the alarm verification process is bypassed).
• Restore each device after testing. For example, if you are testing a pull station,
reset the pull station before testing the next device.
The panel terminates walk test if:
• The zone or device being tested remains inactive for 30 minutes.
• Walk test is stopped by the user.
To start a walk test:
1. Press the menu button and choose Test.
2. Choose Walk Test Silent or Walk Test Audible.
3. Enter a level one password.
4. Choose either All Devices or Zone.
5. If you chose Zone, enter the zone ID for the zone you
are going to conduct the walk test.
6. Choose Start.
7. Conduct your walk test.
8. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Note: To see the activation and restoration of all walk
test events, the panel must be reset prior to ending the
walk test. Once the reset is complete, you can end the
walk test and view a walk test report.