EasyManua.ls Logo

GE Security Vigilant VS2 - Page 21

GE Security Vigilant VS2
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 1: Installation and wiring
Vigilant VS1 and VS2 Technical Reference Manual 9
Vigilant VS1 panel:
3.75 A total, 2.5 A max. per circuit at 120/230 VAC 60 Hz
3.0 A total, 2.5 A max. per circuit at 230 VAC 50 Hz
Vigilant VS2 panel:
6.0 A total, 2.5 A max. per circuit at 120/230 VAC 60 Hz
5.0 A total, 2.5 A max. per circuit at 230 VAC 50 Hz
Max. resistance: 26 total
Max. capacitance: 0.35 µF
EOLR: 15 k, 1/2 W (P/N EOL-15)
Synchronized or not synchronized. For NACs wired Class B, signal synchronization
is supported system-wide (all NAC circuits).
Ground fault impedance: 0 to 5 k
Power-limited and supervised
Notes
On the Vigilant VS1 panel, Class A wiring is available only when the optional SA-
CLA expansion card is installed. Refer to the “SA-CLA Class A Interface Card
Installation Sheet” (P/N 3101094) and to the topic “SA-CLA wiring” on page 22.
Listed EOLRs must be installed as shown for proper supervision.
Marking indicates output signal polarity when the circuit is active. Polarity
reverses when the circuit is not active. Wire notification appliances accordingly.
Notification appliance polarity shown in active state.
Installation limits are subject to acceptance by the Authority Having Jurisdiction
(AHJ).
Figure 10: Terminal wiring location

Table of Contents

Related product manuals