Appendix B: Worksheets
Vigilant VS1 and VS2 Technical Reference Manual 203
Where:
Ia = appliance maximum current
Refer to the appliance installation sheets for Ia. Remember to use the maximum
operating current specified for FWR power.
2. Calculate the minimum voltage (Vm).
Vm = Vs − (Itot × K)
Where:
Vs = source voltage
Itot = total current (from above)
K = load factor
VS1 panel: For the power supply, Vs is 20.4 V and K is
0.20 V/A.
VS2 panel: For the power supply, Vs is 20.4 V and K is 0.24 V/A
3. Calculate the allowable voltage drop (Vd) between the power supply and the
appliances.
Vd = Vm − Va
Where:
Vm = minimum voltage (from above)
Va = appliance minimum voltage
For regulated notification appliances, Va is 16 V. For special application
notification appliances, Va is the lowest operating voltage specified on the
appliance installation sheet.
4. Calculate the maximum resistance (Rmax) for the wire.
Rmax = Vd / Itot
Where:
Vd = voltage drop
Itot = total current
5. Calculate the maximum length of the cable (Lc), based on the maximum
resistance allowed, the resistance of the wire, and the number of wires in the
cable (two).
Lc = (Rmax / Rw) / 2
Where:
Rmax = maximum resistance
Rw = wire resistance factor
Example: You’re using regulated notification appliances. Assume that the maximum
operating current for each appliance is 100 mA for FWR power, and that 20