Chapter 2: Front panel programming
38 Vigilant VS1 and VS2 Technical Reference Manual
Default loop configuration settings
• Loop class: Class B
• Zone
Type: Alarm
Correlation group: 001
Notes
- By default, NACs, zones, and most
devices are assigned to correlation
group 001.
- Relay and sounder bases with the
Follow option set to Head are not
automatically assigned to correlation
groups.
Event notification
Active > Printer: Yes
Active > Dialer: Acct 1
Active > NET: Yes
Active > CID: 110
Trouble > Printer: Yes
Trouble > Dialer: Acct 1
Trouble > NET: Yes
Trouble > CID: 373
Disable > Printer: Yes
Disable > Dialer: Acct 1
Disable > NET: Yes
Disable > CID: 570
Pre alarm > Printer: Yes
Pre alarm > Dialer: None
Pre alarm > NET: No
Pre alarm > CID: 118
Alarm verify > Printer: Yes
Alarm verify > Dialer: None
Alarm verify > NET: No
Alarm verify > CID: 118
Maintenance alert > Printer: Yes
Maintenance alert > Dialer: Acct 1
Maintenance alert > NET: Yes
Maintenance alert > CID: 393
Test > Printer: Yes
Test > Dialer: Acct 1
Test > NET: Yes
Test > CID: 614
• Device
Day sensitivity: Least
Night sensitivity: Least
Day prealarm %: Off
Night prealarm %: Off
Base follow: Alarm
Event notification
Active > Printer: Yes
Active > Coder: 00-00-00-00
Active > Dialer: Acct 1
Active > NET: Yes
Active > CID: 110
Trouble > Printer: Yes
Trouble > Dialer: Acct 1
Trouble > NET: Yes
Trouble > CID: 373
Disable > Printer: Yes
Disable > Dialer: Acct 1
Disable > NET: Yes
Disable > CID: 570
Pre alarm > Printer: Yes
Pre alarm > Coder: 00-00-00-00
Pre alarm > Dialer: None
Pre alarm > NET: No
Pre alarm > CID: 118
Type (input device): Depends on type of device
and marketplace
Type (output device): Genesis with audible/visible
silence
Correlation group: 1
Alarm verify > Printer: Yes
Alarm verify > Coder: 00-00-00-00
Alarm verify > Dialer: None
Alarm verify > NET: No
Alarm verify > CID: 118
Maintenance alert > Printer: Yes
Maintenance alert > Coder: 00-00-00-00
Maintenance alert > Dialer: Acct 1
Maintenance alert > NET: Yes
Maintenance alert > CID: 393
Test > Printer: Yes
Test > Coder: 00-00-00-00
Test > Dialer: Acct 1
Test > NET: Yes
Test > CID: 614

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals