Chapter 2: Front panel programming
Vigilant VS1 and VS2 Technical Reference Manual 71
Device option Description
Heat detectors
Heat alarm: For heat detectors and contact devices. All activations are
immediately considered as alarms. Circuit cannot be restored until devices are
restored to normal and the panel is reset.
Heat alarm RoR: For heat detectors and contact devices with rate-of-rise. All
activations are immediately considered as alarms. Circuit cannot be restored
until devices are restored to normal and the panel is reset.
Input module device types
2Wire Class A: Allows for the monitoring of two-wire conventional smoke
detectors in a Class A circuit (that do not require alarm verification) and normally
open contact initiating devices on the same circuit.
2Wire Class B: Allows for the monitoring of two-wire conventional smoke
detectors in a Class B circuit (that do not require alarm verification) and normally
open contact initiating devices on the same circuit
2Wire verify Class A: Allows for the monitoring of two-wire conventional smoke
detectors in a Class A circuit (that require alarm verification)
2Wire verify Class B: Allows for the monitoring of two-wire conventional smoke
detectors in a Class B circuit (that require alarm verification)
Alarm: For smoke detectors and contact devices. All activations are immediately
considered as alarms. Circuit cannot be restored until devices are restored to
normal and the panel is reset.
Duct alarm: For duct smoke detectors. All activations are immediately
considered as alarms. Circuit cannot be restored until devices are restored to
normal and the panel is reset.
Heat: For heat detectors and contact devices. All activations are immediately
considered as alarms. Circuit cannot be restored until devices are restored to
normal and the panel is reset.
Pull station: For pull station devices. All activations are immediately considered
as alarms.
Remote drill: For a remote switch that when activated, starts the panel’s drill
operation.
Remote reset: For a remote switch that when activated, resets the panel.
Remote signal silence: For a remote switch that when activated, silences the
signaling devices.
Waterflow: For connecting vane type and pressure flow switches. Activations are
considered as alarms. A 16-secondalarm delay applies to waterflow activations.
Circuit cannot be restored until devices are restored to normal and the panel is
reset. Waterflow activations do not invoke in-suite signal silence.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals