Chapter 2: Front panel programming
84 Vigilant VS1 and VS2 Technical Reference Manual
To enable in-suite signal silence for a correlation group:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3 Choose Loop Configuration.
4. Choose Correlation Groups and enter the number of
the correlation group. (Values range from 001 to 199.)
5. Choose Suite Sig Sil.
6. Select:
Yes to enable in-suite signal silence.
No to disable it.
7. Choose Save.
Advanced Program
Loop Configuration
⇩
Loop Configuration
Loop Class
Zone
Correlation Groups
⇩
Correlation Groups
Number 001<>
⇩
Correlation Group 001
Add/Remove Zone
Add/Remove NAC
Add/Remove Device
Suite Sig Sil YES<>
⇩
Correlation Group 001
Copy 001
Remove All
Save
To set the in-suite signal silence elapse timer:
1. Press the Menu button and choose Programming.
2. Choose Panel Operation and enter the level 2
password.
3. For the Suite Sig Sil option, enter a value from 1 to 10
minutes (The default is 10). To disable in-suite signal
silence, set this option to Off.
This is a global option that sets the shutdown period
during which “in suite” evacuation signals outside the
alarm zone remain silenced.
Advanced Program
Panel Operation
⇩
Panel Operation
AC Fail Delay 15<>
Zone Resound On<>
Reset Inhibit 1Min<>
Suite Sig Sil 10<>
⇩
Panel Operation
Evnt Notif ZoneDev<>
AUX Power Reset On<>
LCD Banner >
Save