Chapter 2: Front panel programming
84 Vigilant VS1 and VS2 Technical Reference Manual
To enable in-suite signal silence for a correlation group:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3 Choose Loop Configuration.
4. Choose Correlation Groups and enter the number of
the correlation group. (Values range from 001 to 199.)
5. Choose Suite Sig Sil.
6. Select:
Yes to enable in-suite signal silence.
No to disable it.
7. Choose Save.
Advanced Program
Loop Configuration
Loop Configuration
Loop Class
Zone
Correlation Groups
Correlation Groups
Number 001<>
Correlation Group 001
Add/Remove Zone
Add/Remove NAC
Add/Remove Device
Suite Sig Sil YES<>
Correlation Group 001
Copy 001
Remove All
Save
To set the in-suite signal silence elapse timer:
1. Press the Menu button and choose Programming.
2. Choose Panel Operation and enter the level 2
password.
3. For the Suite Sig Sil option, enter a value from 1 to 10
minutes (The default is 10). To disable in-suite signal
silence, set this option to Off.
This is a global option that sets the shutdown period
during which “in suite” evacuation signals outside the
alarm zone remain silenced.
Advanced Program
Panel Operation
Panel Operation
AC Fail Delay 15<>
Zone Resound On<>
Reset Inhibit 1Min<>
Suite Sig Sil 10<>
Panel Operation
Evnt Notif ZoneDev<>
AUX Power Reset On<>
LCD Banner >
Save

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS2 and is the answer not in the manual?

GE Security Vigilant VS2 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS2
CategoryControl Panel
LanguageEnglish

Related product manuals