GE Power Management 745 Transformer Management Relay 8-47
8 COMMUNICATIONS 8.3 MODBUS MEMORY MAP
8
OUTPUT
RELAY 8
15D0 Output 8 Name (9 registers) --- --- --- F33
Frequency Trip 3
15D9 Output 8 Operation --- --- --- F66
0 = self-resetting
15DA Output 8 Type --- --- --- F38 0 = Trip
15DB Output 8 FlexLogic (20 registers) --- --- --- F47 ---
15EF Reserved
↓↓ ↓
↓↓↓ ↓
15FF Reserved
TRACE
MEMORY
1600 Number of Pre-Trigger Cycles 1 to 15 1 cycles F1 12 cycles
1601
Trace Memory Trigger FlexLogic (10 registers)
--- --- --- F47 ---
160B Reserved
↓↓ ↓
↓↓↓ ↓
19FF Reserved
VIRTUAL
OUTPUTS
1A00 Virtual Output 1 FlexLogic (10 registers) --- --- --- F47 ---
1A0A Virtual Output 2 FlexLogic (10 registers) --- --- --- F47 ---
1A14 Virtual Output 3 FlexLogic (10 registers) --- --- --- F47 ---
1A1E Virtual Output 4 FlexLogic (10 registers) --- --- --- F47 ---
1A28 Virtual Output 5 FlexLogic (10 registers) --- --- --- F47 ---
1A32 Reserved
↓↓ ↓
↓↓↓ ↓
1D7F Reserved
TIMERS 1D80 Timer 1 Start --- --- --- F62 0 = End
1D81 Timer 1 Pickup Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D82 Timer 1 Dropout Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D83 Timer 2 Start --- --- --- F62 0 = End
1D84 Timer 2 Pickup Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D85 Timer 2 Dropout Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D86 Timer 3 Start --- --- --- F62 0 = End
1D87 Timer 3 Pickup Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D88 Timer 3 Dropout Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D89 Timer 4 Start --- --- --- F62 0 = End
1D8A Timer 4 Pickup Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D8B Timer 4 Dropout Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D8C Timer 5 Start --- --- --- F62 0 = End
1D8D Timer 5 Pickup Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D8E Timer 5 Dropout Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D8F Timer 6 Start --- --- --- F62 0 = End
1D90 Timer 6 Pickup Delay 0.00 to 600.00 0.01 s F3 0.00 s
1D91 Timer 6 Dropout Delay 0.00 to 600.00 0.01 s F3 0.00 s
Table 8–6: 745 MEMORY MAP (Sheet 31 of 57)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT