11-12 745 Transformer Management Relay GE Power Management
11.1 COMMISSIONING SUMMARY 11 SETPOINT TABLES
11
W2 Rstd Gnd Fault Slope 10%
W2 Rstd Gnd Fault Delay 0.10 s
W2 Rstd Gnd Fault Block Disabled
W3 Rstd Gnd Fault Function Disabled
W3 Rstd Gnd Fault Target Latched
W3 Rstd Gnd Fault Pickup 0.08 x CT
W3 Rstd Gnd Fault Slope 10%
W3 Rstd Gnd Fault Delay 0.10 s
W3 Rstd Gnd Fault Block Disabled
W1 Rst Gnd Inst O/C Function Disabled
W1 Rst Gnd Inst O/C Target Latched
W1 Rst Gnd Inst O/C Pickup 10.00 x CT
W1 Rst Gnd Inst O/C Delay 0 ms
W1 Rst Gnd Inst O/C Block Disabled
W2 Rst Gnd Inst O/C Function Disabled
W2 Rst Gnd Inst O/C Target Latched
W2 Rst Gnd Inst O/C Pickup 10.00 x CT
W2 Rst Gnd Inst O/C Delay 0 ms
W2 Rst Gnd Inst O/C Block Disabled
W3 Rst Gnd Inst O/C Function Disabled
W3 Rst Gnd Inst O/C Target Latched
W3 Rst Gnd Inst O/C Pickup 10.00 x CT
W3 Rst Gnd Inst O/C Delay 0 ms
W3 Rst Gnd Inst O/C Block Disabled
NEGATIVE SEQUENCE OVERCURRENT
W1 Neg Seq Time O/C Function Disabled
W1 Neg Seq Time O/C Target Latched
W1 Neg Seq Time O/C Pickup 0.25 x CT
W1 Neg Seq Time O/C Shape Ext Inverse
W1 Neg Seq Time O/C Multiplier 1.00
W1 Neg Seq Time O/C Reset Linear
W1 Neg Seq Time O/C Block Disabled
W2 Neg Seq Time O/C Function Disabled
W2 Neg Seq Time O/C Target Latched
W2 Neg Seq Time O/C Pickup 0.25 x CT
Table 11–6: S4 ELEMENTS (Sheet 7 of 12)
DESCRIPTION DEFAULT GROUP 1 GROUP 2 GROUP 3 GROUP 4