GE Power Management 745 Transformer Management Relay 11-13
11 SETPOINT TABLES 11.1 COMMISSIONING SUMMARY
11
W2 Neg Seq Time O/C Shape Ext Inverse
W2 Neg Seq Time O/C Multiplier 1.00
W2 Neg Seq Time O/C Reset Linear
W2 Neg Seq Time O/C Block Disabled
W3 Neg Seq Time O/C Function Disabled
W3 Neg Seq Time O/C Target Latched
W3 Neg Seq Time O/C Pickup 0.25 x CT
W3 Neg Seq Time O/C Shape Ext Inverse
W3 Neg Seq Time O/C Multiplier 1.00
W3 Neg Seq Time O/C Reset Linear
W3 Neg Seq Time O/C Block Disabled
W1 Neg Seq Inst O/C Function Disabled
W1 Neg Seq Inst O/C Target Latched
W1 Neg Seq Inst O/C Pickup 10.00 x CT
W1 Neg Seq Inst O/C Delay 0 ms
W1 Neg Seq Inst O/C Block Disabled
W2 Neg Seq Inst O/C Function Disabled
W2 Neg Seq Inst O/C Target Latched
W2 Neg Seq Inst O/C Pickup 10.00 x CT
W2 Neg Seq Inst O/C Delay 0 ms
W2 Neg Seq Inst O/C Block Disabled
W3 Neg Seq Inst O/C Function Disabled
W3 Neg Seq Inst O/C Target Latched
W3 Neg Seq Inst O/C Pickup 10.00 x CT
W3 Neg Seq Inst O/C Delay 0 ms
W3 Neg Seq Inst O/C Block Disabled
FREQUENCY
Underfrequency 1 Function Disabled
Underfrequency 1 Target Self-reset
Current Sensing Enabled
Underfrequency 1 Min. Current 0.20 x CT
Minimum Operating Voltage 0.50 x VT
Underfrequency 1 Pickup 59.00 Hz
Underfrequency 1 Delay 1.00 s
Underfrequency 1 Block Disabled
Table 11–6: S4 ELEMENTS (Sheet 8 of 12)
DESCRIPTION DEFAULT GROUP 1 GROUP 2 GROUP 3 GROUP 4