GE Power Management 745 Transformer Management Relay 11-17
11 SETPOINT TABLES 11.1 COMMISSIONING SUMMARY
11
Analog Level 1 Target Self-reset
Analog Level 1 Pickup 10 mA
Analog Level 1 Delay 50 s
Analog Level 1 Block Disabled
Analog Level 2 Function Disabled
Analog Level 2 Target Self-reset
Analog Level 2 Pickup 100 mA
Analog Level 2 Delay 100 s
Analog Level 2 Block Disabled
CURRENT DEMAND
W1 Current Demand Function Disabled
W1 Current Demand Target Self-reset
W1 Current Demand Pickup 100 A
W1 Current Demand Block Disabled
W2 Current Demand Function Disabled
W2 Current Demand Target Self-reset
W2 Current Demand Pickup 400 A
W2 Current Demand Block Disabled
W3 Current Demand Function Disabled
W3 Current Demand Target Self-reset
W3 Current Demand Pickup 400 A
W3 Current Demand Block Disabled
TRANSFORMER OVERLOAD
Xformer Overload Function Disabled
Xformer Overload Target Self-reset
Xformer Overload Pickup 208%
Xformer Overload Delay 10 s
Xformer Overload Block Disabled
Overtemp Alarm Signal Disabled
Tap changer failure
Tap changer failure Function Disabled
Tap changer failure Target Self-Reset
Tap changer failure Delay 5.0 s
Tap changer failure Block Disabled
Table 11–6: S4 ELEMENTS (Sheet 12 of 12)
DESCRIPTION DEFAULT GROUP 1 GROUP 2 GROUP 3 GROUP 4