INTERNAL BUZZER SILENCE
SYSTEM RESET
LAMP TEST - General User Access (no code entry required)
ALARMS SILENCE/RESOUND
AUXILIARY RELAYS (DISABLEMENTS)
SOUNDERS ENABLE/DISABLE
SELECTED DETECTORS (DISABLEMENTS)
The occurrence of any new fire or fault condition will initiate the operation of the internal buzzer. By pressing this switch,
the operation of the buzzer will be stopped until a new fire or fault appears on the system.
Soft resets the entire system. A soft reset should be satisfactory under almost all circumstances however a Master Reset
can be performed using the PCB mounted switch on the main PCB (not shown) or by cycling the power on the Main Panel
(removing both primary AC and secondary DC supplies).
NOTE:
before the SYSTEM RESET button will operate.
Lights all the LEDS, turns on the LCD back light and sets all display pixels to black.
Lamp test only operates whilst the key is depressed.
Activates all sounders. A second press de-activates all sounders.
The button LED (RED) is illuminated whilst the sounders are activated.
It is possible to define if pressing this button will activate the systems Fire I/O units.
Delayed sounder circuits. Pressing this button while the sounder delay is taking place, will also stop. This operation will
not stop the evacuation timer.
When this button is activated all relays and I/O modules connected to the system have their outputs disabled. This
includes the normally energised FAULT relay, the FAULT I/O group and all ALARM I/O groups. When these outputs are
disabled the button LED is illuminated. Pressing the button again restores normal relay and I/O module operation.
NOTE: IF I/O'S ARE TO BE ACTIVATED BY EVAC. CONDITION, THIS WILL OVERRIDE THE
DISABLEMENT
Pressing this button will enable/ disable all sounders both conventional sounder circuits and addressable sounders.
Via the programming menus individual sensors may have selective disablement turned on. When this button is
activated those sensors that have selective disablement turned on will not generate a fire alarm condition. When
activated the button LED is illuminated.
If no devices have selective disablement turned on then this button press will have no effect.
Pressing the button again restores normal sensor operation.
if an alarm has been detected it is necessary to silence the alarms using SOUNDER SILENCE