DELAYS ACTIVE
FIRE (QUEUE REVIEW) - General User Access (no code entry required)
FAULT (QUEUE REVIEW) - General User Access (no code entry required)
TEST (QUEUE REVIEW) - General User Access (no code entry required)
DISABLED (QUEUE REVIEW) - General User Access (no code entry required)
PAPER FEED
Pressing this button will activate any pre-programmed delays. The yellow LED associated with this button and the
general disablements led will both be lit. A second press of this button will de-activate the delays and the led.
Under any fire condition the delays will be activated. If during the course of these delays this button is pressed the delays
will be overridden and the sounders and together with any other fire indicating equipment, will be activated.
If more than one fire has been detected then the LED next to this button will flash. Press the button to step through all
detected fires. Once all fires have been reviewed the LED will be constantly illuminated. Subsequent fires will be added to
the end of the queue and the LED will start to flash again.
After each button press the information will be displayed for 20 seconds. After that time the screen will revert back to the
first fire.
If more than one fault has been detected, or if a fault and fire have been detected, then the LED next to this button will
flash. Press the button to step through all reported faults. Once all faults have been reviewed the LED will be constantly
illuminated. Subsequent faults will be added to the end of the queue and the LED will start to flash again.
After each button press the information will be displayed for 20 seconds. After that the screen will revert back to the first
fault (or fire).
If the LED next to this button is illuminated then a test mode has been selected via the programming menus. Pressing the
button will show which sounders and zones have been set to test mode. If there are more zones under test than can be
displayed then pressing the button again will show the next set of zones under test.
The information is displayed for 15 seconds before the default display is restored.
NOTE: a SYSTEM RESET will clear all test modes.
If the LED next to this button is illuminated then there is at least one disablement active in the system. Pressing the
button will display the disablements. If there are more disablements that can be displayed then pressing the button
again will show the next set of disablements and so on.
The information is displayed for 15 seconds before the default display is restored.
Possible disablements include - printer, fire brigade transmission, auxiliary relays, loops, zones, detectors and sounders.
Each press feeds a single line of paper through the printer.
51
Manufacturers of Fire Detection Equipment
INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013
JUNO NET - NETWORKABLE ADRESSABLE PANEL