COMMAND DETAILS
47
Return Parameter <NR1> Sound
0 Off
1 On
Query Example :UTILITY:SOUN?
0
Sound is currently set to
off.
:UTILITY:REMote
System Command
Description
Turns the remote control on or off.
Syntax :UTILITY:REMote OFF/0, ON/1
Parameter OFF/0, ON/1
OFF/0 Turns Remote control off
ON/1 Turns remote control on
Example :UTILITY:REM 1
Turns remote control on.
:UTILITY:REMote:MODE
System Command
Description
Sets the remote mode to fast or normal. When in
fast mode, the panel interface is deactivated with
an interface time of no more than 10ms. Normal
mode has an interface time of 30~130ms. In normal
mode the display interface continues to update the
screen in real-time.
Syntax :UTILITY:REMote:MODE NORMAL/0, FAST/1
Parameter NORMAL/0, FAST/1 Mode
NORMAL/0 NORMAL
FAST/1 FAST
Example :UTILITY:REM:MODE 1
Turns remote mode to
fast.
PEL-2000 Programming Manual
48
:UTILITY:TIME
System Command
Description
Sets the date and time on the mainframe.
Syntax :UTILITY:TIME [aard]
Parameter [aard]
1
2
3
Year
Month/Day
Time (24 hours)
Example :UTILITY:TIME “200901031343”
Sets the time to 1:00 pm, January 3
rd,
2009.
Query Syntax :UTILITY:TIME?
Return Parameter [aard]
1
2
3
Year
Month/Day
Time (24 hours)
Query Example :UTILITY:TIME?
2009/11/13/13:00
The date is November
13
th
, 2009. The time is
1:00 pm.
:UTILITY:LOAD
System Command
Description
Sets the knob control style.
he load module control
knobs can be set to operate independently (OLD style) to
the mainframe or with the mainframe (UPDATED).
Syntax :UTILITY:LOAD OLD/0, Updated/1
Parameter OLD/0, UPDATED/1 Knob style
OLD/0 Old
UPDATED/1 Updated
Example :UTILITY:LOAD 1
Set the knob style to
independent.
Query Syntax :UTILITY:LOAD?