WTX110 A4774-1.0 HBM: public 145
Information
This setting is ignored in a downwards weighing
10.2.16 Coarse flow cut-off point Crs.Fl.off
The coarse flow cut-off point must not be higher than the fine flow cut-off point.
After the target weight is entered, the coarse flow cut-off point is automatically
set to 50% of the target weight if no coarse flow cut-off point is set. If
optimization is activated (parameter P1 > 0), the coarse flow cut-off point is
tracked automatically. The coarse flow cut-off point must not be higher than the
fine flow cut-off point.
The minimum fine flow may define a minimum distance to the fine flow cut-off
point:
Coarse flow cut-off point
max
=
Fine flow cut-off point – minimum fine flow
10.2.17 Coarse flow monitoring (Crs. Monitor)
This option is used for breakage monitoring during the coarse flow phase (sack
breakage). Enter the increase in weight you expect per time interval (Coarse
monitor) in a normal filling process. At the end of the coarse flow lockout time,
the increase is checked after each time interval (Coarse monitor). If the weight
increase rate is not exceeded, the fact is interpreted as a breakage of the
container being filled, and dosing is aborted. The coarse flow monitor is only
active during the coarse flow phase.
10.2.18 Fine low cut-off point (Fine fl.off)
Sets or reads the fine flow cut-off point. If you specify a target weight, the fine
flow cut-off point is automatically set to 95% of the target weight if no fine flow
cut-off point is set.