Supervisorī˜‚mode
WTX110 A4774-1.0 HBM: public 151
Information
Choose an increase in weight that is greater than the fluctuations caused by
the material escaping during the filling process.
When a break is detected:
S Coarse flow and fine flow are deactivated.
S if bit 6 (Alarm) is set to 1 in dosing status (SDO),
S then if Alarm:Fill flow On is set, the alarm is triggered,
S dosing control goes to stop status.
10.2.30 Lock out time fine flow (Lock fine(s))
The time starts when the coarse flow cut-off point is reached. For the specified
time, the comparison of the actual weight against reaching of the fine flow cut-
off point is disabled. The time does not delay the filling process.
When the coarse flow shuts off, settling processes may occur that will already
cause the coarse flow cut-off point to be exceeded. You can prevent that with
this setting. Experience shows that the lockout time should be about 10 % of
the fine flow dosing time.