Installation
52 A4774-1.0 HBM: public WTX110
Parameters Type Low batt. (volts)
(flashing battery
symbol beginning at
about)
Power off (volts)
(shutdown at about)
Pb12 12 V lead
rechargeable
battery
11.5 V 11 V
Pb24 24 V lead
rechargeable
battery
23 V 22 V
Adjust Any recharge
able battery
Adjustable Adjustable
Line Mains operation - -
If there is only a little remaining capacity (Low batt) the user is alerted by a
flashing battery icon in the top right corner of the display that the rechargeable
battery must be charged.
To prevent deep discharge of the connected rechargeable battery, the terminal
automatically switches off at the set voltage (Power off). If the terminal is
turned on again with the rechargeable battery deeply discharged, a message
appears indicating 'Low Battery: Power off' and the terminal switches off again.
4.17 Legal for trade data storage/alibi memory
If a WTX110 with the ALI option was ordered, the legal for trade memory is
completely pre-wired and plugged into the ASM slot. It is used for storing the
last 1,000,000 weighing processes.
K-WTX110-*-***-**-***-**-ALI-**