1/01 UDC3300 Limit Controller Product Manual 63
6.4 Input #1 Set Up Wiring, Continued
RTD inputs
Use the copper leads and connect the calibrator to the rear terminals of
Input #1. See Figure 6-4.
Figure 6-4 Wiring Connections for RTD (Resistance Thermometer
Device)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
L1
L2/N
22
23
24
25
26
27
R
+
Decade
Resistance
Box
Copper Leads
equal length
22629
Continued on next page