1/01 UDC3300 Limit Controller Product Manual 89
7.8 Parts Replacement Procedures, Continued
Digital input board
Follow the procedure listed in Table 7-17 to replace the Digital Input
boardP/N 30756696-501.
Table 7-17 Digital Input Board Replacement Procedure
Step Action
1
Remove the chassis from the case. See Figure 7-1.
2
Remove the printed wiring boards from the chassis. See Figure 7-3.
3
Lay the boards flat and identify the Digital Input board. See Figure 7-4.
4
Remove the transformer plug from connector J9.
5
Locate the three mounting posts under the MCU/Output board that attach
the Digital Input board to the MCU/Output board.
6
Use small pliers and squeeze the ends of each post together and push it
up through the board. Remove the Digital Input board.
7
Orient the new Digital Input board onto the MCU/Output board and push
the mounting posts down through the MCU/Output board until they click
into place.
8
Replace the transformer plug onto connector J9.
9
Slide the printed wiring boards back into the chassis. Make sure the
connections to the display/keyboard assembly are made and that the
release points on the chassis snap into place on the printed wiring boards.
10
Reinstall the chassis into the case. Push in hard, then tighten the screw.
Continued on next page

Table of Contents

Other manuals for Honeywell UDC3300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC3300 and is the answer not in the manual?

Honeywell UDC3300 Specifications

General IconGeneral
BrandHoneywell
ModelUDC3300
CategoryController
LanguageEnglish

Related product manuals