42 UDC3300 Limit Controller Product Manual 1/01
4.6 Alarms Set Up Group
Introduction
An alarm is an indication that an event that you have configured (for
exampleProcess Variable) has exceeded one or more alarm limits. There
are two alarms available. Each alarm has two setpoints. You can configure
each of these two setpoints to alarm on various controller parameters.
There are two alarm output selections, High and Low. You can configure
each setpoint to alarm either High or Low. These are called single alarms.
You can also configure the two setpoints to alarm on the same event and
to alarm both high and low. A single adjustable Hysteresis of 0.0% to
5.0% is configurable for the alarm setpoint.
Alarms group
prompts
Table 4-5 lists all the function prompts in the “ALARMS” Set Up group
and their definitions.
Table 4-5 Alarms Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
A1S1 VAL
Value in Engineering Units ALARM 1 SETPOINT 1 VALUEThis is the value at
which you want the alarm type chosen in Prompt
"A1S1TYPE" to actuate. The value depends on what the
setpoint has been configured to represent. NO setpoint is
required for Communications SHED.
A1S2 VAL
Value in Engineering Units ALARM 1 SETPOINT 2 VALUEThis is the value at
which you want the alarm type chosen in Prompt
"A1S2TYPE" to actuate.
The details are the same as A1S1 VAL.
A2S1 VAL
Value in Engineering Units ALARM 2 SETPOINT 1 VALUEThis is the value at
which you want the alarm type chosen in Prompt
A2S1TYPE to actuate.
The details are the same as A1S1 VAL.
A2S2 VAL
Value in Engineering Units ALARM 2 SETPOINT 2 VALUEThis is the value at
which you want the alarm type chosen in Prompt
A2S2TYPE to actuate.
The details are the same as A1S1 VAL.
A1S1TYPE
NONE
PV
DEV
SHED
ALARM 1 SETPOINT 1 TYPESelect what you want
Setpoint 1 of Alarm 1 to represent. It can represent the
Deviation or Input 1, and if you have a model with
communications, you can configure the controller to alarm
on SHED.
NO ALARM
INPUT 1
DEVIATION
SHED FROM COMMUNICATIONS
Continued on next page

Table of Contents

Other manuals for Honeywell UDC3300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC3300 and is the answer not in the manual?

Honeywell UDC3300 Specifications

General IconGeneral
BrandHoneywell
ModelUDC3300
CategoryController
LanguageEnglish

Related product manuals