Category Item Specications
Acoustic noise The data listed in the following is the declared
A-weighted sound power levels (LWAd) and
declared average bystander position A-
weighted sound pressure levels (LpAm) when
the server is operating in a 23°C (73.4°F)
ambient environment. Noise emissions are
measured in accordance with ISO 7779 (ECMA
74) and declared in accordance with ISO 9296
(ECMA 109).
Idle:
LWAd: 6.6 Bels
LpAm: 50.0 dBA
Operating:
LWAd: 6.9 Bels
LpAm: 52.7 dBA
NOTE
The actual sound levels generated during server
operating vary depending on the server
conguration, load, and ambient temperature.
Corrosive air
pollutant
Corrosion rate of the copper test piece: <
300 Å/month (in compliance with the
ANSI/ISA-71.04-2013 gaseous corrosion
level G1)
Corrosion rate of the silver test piece: < 200
Å/month
Particulate
pollutant
The ISO14664-1 Class 8 requirements are
met.
You are advised to ask a professional
organization to monitor particulate
pollutants in the equipment room.
There is no explosive, conductive, magnetic,
or corrosive dust in the equipment room.