Category Item Specications
Power supply
unit (PSU)
input
specications
Input voltage 2500 W DC PSU: –48 V DC to –60 V DC
NOTE
The following requirements must be met when this
PSU is used:
Standard ring tongue terminals must be used.
It is recommended that wire gauge be 16 or
larger and thermal resistance be 105ºC or above.
After crimping a power cable, wrap the power
cable using tapes to avoid contact with the
handle.
2000 W AC PSU:
90 V AC to 264 V AC at 50 Hz or 60 Hz
240 V DC
3000 W AC PSU:
90 V AC to 264 V AC at 50 Hz or 60 Hz
240 V DC
NOTE
The recommended current
specications for the
external power circuit breaker connected to the
RH8100 V3 are as follows:
AC: 32 A
DC: 63 A
380 V HV DC: 32 A
Input current
2500 W DC PSU: 63 A
2000 W AC/DC PSU: 10 A
3000 W AC/DC PSU: 16 A
NOTE
A 2000 W PSU uses a 25 A internal fuse.
PSU output
specications
Rated output
voltage
12 V DC
RH8100 V3 Server
User Guide 2 About the RH8100 V3
Issue 30 (2019-12-19) Copyright © Huawei Technologies Co., Ltd. 78