Parameter List
10
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
F0‑15 0xF00F Carrier frequency 0.8 kHz to 16.0 kHz 6 kHz In real time "
F0‑15
"
on
page 102
F0‑16 0xF010 Carrier frequency
adjusted with
temperature
0: No
1: Yes
1 In real time "
F0‑16
"
on
page 102
F0‑17 0xF011 Acceleration time
1
0.0s to 6500.0s 20 s In real time "
F0‑17
"
on
page 102
F0‑18 0xF012 Deceleration time
1
0.0s to 6500.0s 20 s In real time "
F0‑18
"
on
page 103
F0‑19 0xF013 Acceleration/
Deceleration time
unit
0: 1s
1: 0.1s
2: 0.01s
1 At stop "
F0‑19
"
on
page 103
F0‑21 0xF015 Offset frequency of
auxiliary frequency
source upon
superposition
0.00 Hz to F0‑10 0 Hz In real time "
F0‑21
"
on
page 104
F0‑22 0xF016 Frequency
reference
resolution
1: 0.1 Hz
2: 0.01 Hz
2 At stop "
F0‑22
"
on
page 104
F0‑23 0xF017 Retention of
digital setting of
frequency upon
stop
0: Non‑retentive
1: Retentive
0 In real time "
F0‑23
"
on
page 104
F0‑25 0xF019 Acceleration/
Deceleration time
base frequency
0: Maximum frequency (F0‑10)
1: Frequency reference
2: 100 Hz
0 At stop "
F0‑25
"
on
page 105
F0‑26 0xF01A Base frequency for
UP/DOWN
modification
during running
0: Running frequency
1: Frequency reference
0 At stop "
F0‑26
"
on
page 105
F0‑27 0xF01B Main frequency
coefficient
0.00% to 100.00% 10 % In real time "
F0‑27
"
on
page 105
F0‑28 0xF01C Auxiliary frequency
coefficient
0.00% to 100.00% 10 % In real time "
F0‑28
"
on
page 106
F1‑00 0xF100 Motor type
selection
0: Common asynchronous
motor
1: Variable frequency
asynchronous motor
2: Synchronous motor
0 At stop "
F1‑00
"
on
page 106
F1‑01 0xF101 Rated motor
power
0.11000.0 kW 1.5 kW At stop "
F1‑01
"
on
page 106
F1‑02 0xF102 Rated motor
voltage
1 V to 2000 V 380 V At stop "
F1‑02
"
on
page 107
F1‑03 0xF103 Rated motor
current
0.16553.5 A 9 A At stop "
F1‑03
"
on
page 107