Parameter List
‑9‑
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
F0‑07 0xF007 Frequency source
superposition
selection
Ones (position): Frequency
reference selection
0: Main frequency reference X
1: Main and auxiliary
operation result (based on
tens position)
2: Switchover between the
main frequency X and the
auxiliary frequency Y
3: Switchover between the
main frequency X and the
main and auxiliary operation
result
4: Switchover between the
auxiliary frequency Y and the
main and auxiliary operation
result
Tens (position): Main and
auxiliary operation of the
frequency reference
0: Main + Auxiliary
1: Main Auxiliary
2: Max. (main, auxiliary)
3: Min. (main, auxiliary)
4: Main x Auxiliary
0 In real time "
F0‑07
"
on
page 98
F0‑08 0xF008 Preset frequency 0.00 Hz to F0‑10 50 Hz In real time "
F0‑08
"
on
page 99
F0‑09 0xF009 Running direction 0: Same as the default
direction
1: Reverse to the default
direction
0 In real time "
F0‑09
"
on
page 100
F0‑10 0xF00A Maximum
frequency
5.00 Hz to 599.00 Hz 50 Hz At stop "
F0‑10
"
on
page 100
F0‑11 0xF00B Source of
frequency upper
limit
0: F0‑12 (Frequency upper
limit)
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: Communication
6: Multi‑speed reference
0 At stop "
F0‑11
"
on
page 100
F0‑12 0xF00C Frequency upper
limit
F0‑14 to F0‑10 50 Hz In real time "
F0‑12
"
on
page 101
F0‑13 0xF00D Frequency upper
limit offset
0.00 Hz to F0‑10 0 Hz In real time "
F0‑13
"
on
page 101
F0‑14 0xF00E Frequency lower
limit
0.00 Hz to F0‑12 0 Hz In real time "
F0‑14
"
on
page 101