Commissioning
5.7 Change of the terminal assignment
5-10
L
EDSVS9332S-C EN 3.0
5.7 Change of the terminal assignment
If the configuration is changed via C0005, the assignment of all inputs and outputs is overwritten with
the corresponding basic assignment. If necessary, the function assignment must be adapted to the
wiring.
Tip!
For this, use the menu ”Terminal I/O” if the 9371BB operating module is used or the menu ”Terminal
I/O” with Global Drive Control or LEMOC2.
Stop!
If you reassign an input, the signal source that has been assigned up to now will not be overwritten!
The active connection that are not required must be removed.
5.7.1 Freely assignable digital inputs
Five freely assignable digital inputs are available (X5/E1 ... X5/E5). You can define a polarity for each
input. With this you can determine the input to be HIGH active or LOW active.
Change assignment:
Tip!
Use the submenu ”DIGIN” at the 9371BB operating module or the submenu ”Digital inputs” inGlobal
Drive Control or LEMOC2.