Installation
Electrical installation
4.2.13 Connection of feedback systems
4-47
L
EDSVS9332S-B EN 3.0
4.2.13 Connection of feedback systems
Different feedback systems can be connected to the controller:
z Resolver feedback to X7 (Lenze setting)
z Encoder feedback to X8 or X9
Incremental encoder TTL
–Sin/cosencoder
Sin/cos encoder with serial communication (single-turn)
Sin/cos encoder with serial communication (multi-turn)
Resolver signal or encoder signal can be output for slaves at the master frequency output X10.
The connection must be made as shown in the figures:
z Use twisted pair cables and shielded pair cables.
z Connect the shield at both ends.
z Use indicated cable cross-sections.
The feedback system is activated in code C0025.
Note!
z Use a sin/cos encoder with serial communication (multi-turn) if you cannot
reference the drive. Indicate the motor/encoder combination with your order.
z Please observe the notes concerning feedback monitoring in
chapter Troubleshooting and fault elimination”
chapter Configuration/monitoring” of the System Manual