Technical data
3.2 General data/operating conditions
3-2
L
EDSVS9332S-B EN 3.0
3.2 General data/operating conditions
Standards and operating conditions
Conformity CE Low-Voltage Directive (73/23/EEC)
Approvals
UL508 Industrial Control Equipment
UL508C Power Conversion Equipment
Underwriter Laboratories (File No. E132659)
for USA and Canada
Vibration resistance Germanischer Lloyd, general conditions
Climatic conditions Class 3K3 to EN50178 (without condensa tion, average relative humidity 85%)
Degree of pollution VDE 0110 part 2 pollution degree 2
Packaging (DIN 4180) Delivery packing
Permissible temperature
Transport -25°C...+70°C
ranges
Storage -20°C...+55°C
Operation
Types 9321 ... 9326 0°C...+55°C
reduce the rated output current by 2.5%/°C above
Types 9327 ... 9332 0°C...+50°C
+40 °C
Permissible installation height 0 ... 4000 m amsl reduce the rated output current by 5%/1000 m above
1000 m amsl
Mounting positions Vertical
DC-bus operation Possible
General e lectrical data
EMC Compliance with EN 61800-3/A11
Noise emission Requirements to EN 50081-2, EN 50082-1, EN 61800-3
Limit value class A to EN 55011 (industrial area) with mains filter A
Limit value class B to EN 55022 (residential area) with mains filter B and installation in control cabinet
Noise immunity
Limit values maintained using mains filter.
Requirements to EN 50082-2, EN 61800-3
Requirements Standard Severities
ESD EN61000-4-2 3, i.e. 8 kV with air discharge
6 kV with contact discharge
RF interference (enclosure) EN61000-4-3 80 MHz ... 1000 MHz, 10 V/m 80 % AM (1 kHz)
Burst EN61000-4-4 3/4, i.e. 2 kV/5 kHz
Surge
(Surge on mains cable)
EN61000-4-5 3, i.e. 1.2/50 μs,
1 kV phase-phase, 2 kV phase-PE
Insulation resistance Overvoltage category III to VDE 0110
Discharge current to PE (to EN 50178) >3.5mA
Enclosure
IP20
IP41 on the heatsink side for thermal separation (push-through technique)
NEMA 1: Shock protection
Protective insulation of control circuits Safe mains isolation: Double/reinforced insulation to EN 50178 for digital inputs and outputs