Commissioning
5.2 Input of the motor data
5-4
L
EDSVS9332S-C EN 3.0
5.2 Input of the motor data
To achieve an optimum speed-torque behaviour of the drive, it is necessary to enter the nameplate
data of the connected motor.
z If a LENZE motor is used:
– Select the motor type under C0086 (see chapter 9.4; code table or chapter 9.5.3; motor
selection list). All other motor data are automatically set by the controller.
– To achieve outstanding accuracy you can enter the eight-digit designation of the motor
nameplate ”encoder” under C0416 when using motors with resolvers (optional).
z If the motor type is not included in the list under C0086, select a Lenze motor with similar data
in C0086 (see chapter 9.4; code table or chapter 9.5.3; motor selection list). The following
motor data must be altered manually:
– C0006: Operating mode of the motor control
– C0022: Adapt I
max
to the max. motor current
– C0081: Rated motor power
– C0087: Rated motor speed
– C0088: Rated motor current
– C0089: Rated motor frequency
– C0090: Rated motor voltage
– C0091: Motor cos
ϕ
– User-specific detection of the motor temperature (see chapter 4.2.8)
Only for very high demands on the control features:
– C0084: Stator resistance of the motor
– C0085: Leakage inductance of the motor
Tip!
z All required inputs are contained in the menu ”Motor/feedb.”(Motor/feedback system”).
z If you select a motor type under C0086 and change one of the above listed motor data
subsequently, C0086 = o (COMMON) is set (i.e. no Lenze motor is used).
z Do not operate reluctance motors.