Troubleshooting and fault elimination
10.4 Resetting fault indications
10-10
L
EDSVS9332S-E EN 3.0
10.4 Resetting fault indications
Reaction on
operating errors
Measures for re-commissioning Danger notes
TRIP After the error has been eliminated, the drive can be restarted when an
acknowledgement has been sent.
Acknowledge TRIP by:
Global-Drive-Control: Click ”Trip reset” in dialog box ”Diagnostics 9300”. (
10-4, (“Working with the history buffer”))
XT keypad: Press
. Then press to enable the controller.
Fieldbus module: Set C0043 = 0
Control word C0135
Terminal X5/E5 (default setting) or “DCTRL-TRIP-RESET”
Control word AIF
Control word system bus (CAN)
If a TRIP source is still active, TRIP cannot be reset.
Message After eliminating the fault, the message is reset automatically.
The drive restarts automatically if the message is
removed.
Warning After eliminating the fault, the warning is reset automatically.