Preface and general information
EC Directives/Declaration of conformity
1.3.4 EC Directive on electromagnetic compatibility
1-6
L
EDSVS9332S-A EN 3.0
1.3.4 EC Directive on electromagnetic compatibility
(89/336/EWG)
amended by:
z First Amendment Directive (92/31/EWG)
z CE Mark Directive (93/68/EWG)
1.3.4.1 General
z The EC Directive Electromagnetic Compatibility” applies to devices” which may cause
electromagnetic interferences or the operation of which may be impaired by such
interferences.
z The aim is to limit the generation of electromagnetic interferences such that radio and
telecommunication systems and other equipment can be operated without interferences.
Furthermore the devices must show an appropriate resistance against electromagnetic
interference to ensure the application as directed.
z Controllers cannot be operated on their own. Controllers cannot be evaluated on their own in
terms of EMC. Only when being integrated into a drive system the compliance with the
objectives of the EC Directive EMC and the observance of the Law on electromagnetic
compatibility of devices” can be checked.
z Lenze has evaluated the conformity of the controllers in defined drive systems. In the
following, these evaluated drive systems are called CE-typical drive system”. Therefore the
user of the controllers can
either determine the system components and their integration into a drive system and
declare the conformity on his own responsibility,
or install the drive system according to the CE-typical drive system evaluated by the inverter
manufacturer who already proved the conformity.
Components of the CE-typical drive system
System component Specification
Controller Controller types 93XX series
For type designation see first cover page
Mains filter A/B For data and filter assignment see chapter ”Ratings”
Motor cable Shielded power cable with tinned E-CU braid with a minimum of 85% optical coverage.
Mains cable between mains filter
and controller
From a minimum cable length of 300 mm:
Shielded power cable with tinned E-CU braid with a minimum of 85% optical coverage.
Control cables Shielded signal cable type LIYCY
Motor Standard three-phase asynchronous motor, servo synchronous motor, servo asynchronous motor
Lenze types DXRA, MDXKX or similar
z Controller, RFI filter and mains choke are located on a common mounting plate.
z The system components have been wired according to chapter 4 Electrical installation”.

Table of Contents