EasyManua.ls Logo

Lenze EVS 9300 series - First Order Derivative-Action Element (DT1)

Lenze EVS 9300 series
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function library
Function blocks
9.2.32 First order derivative-action element (DT1)
9-120
L
EDSVS9332S-D11 EN 3.0
9.2.32 First order derivative-action element (DT1)
Purpose
Derivative action of signals.
For instance, used for the speed injection (dv/dt).
DT1-1
DT1-1-OUT
DT1-1-IN
C0654
C0651
C0652
±199.99 %
C0653
C0650
fb_dt1-1
Fig. 9-80 First order derivative-action element (DT1-1)
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
DT1-1-IN a C0654 dec [%] C0652 1 1000 -
DT1-1-OUT a - - - - - limited to ±199.99 %
Function
z The gain is set under C0650.
z The delay T
v
is set under C0651.
z The input sensitivity of the DT1-1 element can be reduced under C0653.
z The FB only evaluates the specified most significant bits, according to the setting.
t
T
v
K=T
d
/T
v
Fig. 9-81 Delay time T
v
of the first order derivative-action element

Table of Contents