Parameter setting
Parameter setting using the keypad
7-7
l
EDSVS9332S-D11 EN 3.0
7.2.6 Parameter set transfer
Parameter settings can be easily copied from one basic device to another by using the keypad.
For this purpose use the menu ”Load/Store”:
Danger!
During the parameter transfer from the keypad to the basic device the control
terminals can adopt undefined states!
Therefore the plugs X5 and X6 must be disconnected from the basic device before
the transfer takes place. This ensures that the controller is inhibited and all control
terminals have the defined state ”LOW”.
Copying parameter sets from the basic device into the keypad
Step Key sequence Action
1. Connect the keypad to the basic device 1
2. Inhibit controller: Terminal X5/28 = LOW
The drive coasts.
3. Select C0003 in the menu ”Load/Store” C0003
Select the code C0003 ”PAR SAVE” in the menu ”Load/Store” using
the arrow keys.
4. Change to the parameter level
Display ”0” and ”READY”
5. Copy all parameter set into the keypad
The settings stored in the keypad are overwritten.
Set ”11” ”Save extern”
6. Start copying
”RDY” goes OFF. ”BUSY” is displayed.
If ”BUSY” goes OFF after approx. one minute, all parameter sets have
been copied into the keypad.
7.
Change to the code level
A)
Display of the operating level
B)
Display C0003 and ”PAR SAVE”
8. Enable controller Terminal X5/28 = HIGH
9. Remove keypad from the basic device 1