Parameter setting
Parameter setting using the keypad
7-6
l
EDSVS9332S-D11 EN 3.0
7.2.5 Parameter set loading
You can use the keypad to load a saved parameter set into the RAM when the controller is inhibited.
After controller enable the controller uses the new parameters.
Danger!
z After loading a new parameter set the controller will be initialised again and
behavesasifthemainswasswitchedon:
System configurations and terminal assignments may be changed. Ensure that
your wiring and drive configuration correspond to the settings of the parameter
set.
z Only use terminal X5/28 as source for the controller inhibit! Otherwise, the drive
can start in an uncontrolled way when changing to another parameter set.
Note!
z After connecting the supply voltage the controller always loads parameter set 1
into the RAM.
z You can also load other parameter sets into the RAM via the digital inputs or bus
commands.
Step Keys Action
1. Inhibit controller Terminal X5/28 = LOW
2.
Load saved parameter set into the RAM
A)

Select code C0002 ”PAR LOAD in the menu ”Load/Store”
B)
Change to parameter level
Display ”0” and ”Load Default”
If you want to return to the state as delivered, proceed with D)
Select parameter set to be loaded C)
Load parameter set 1:
Ö Set ”1” ”Load PS1”
Load parameter set 2:
Ö Set ”2” ”Load PS2”
Load parameter set 3:
Ö Set ”3” ”Load PS3”
Load parameter set 4:
Ö Set ”4” ”Load PS4”
D)

”RDY” is off. The parameter set has been completely loaded into the RAM when
RDY”isonagain.
3.
Change to the code level
A)
Display of operation level
B)
Display C0002 ”PAR LOAD”
4. Enable the controller. Terminal X5/28 = HIGH
The drive is now running with the settings of the loaded parameter set