Installation
Electrical installation
4.2.8 Motor temperature monitoring
4-32
L
EDSVS9332S-B EN 3.0
4.2.8 Motor temperature monitoring
Stop!
z Do not connect an external voltage to the terminals T1, T2. Otherwise the controller will be
damaged.
z Do not use the terminals T1, T2 for safety-relevant wiring. Fault messages via this input are
only processed after 2 s.
Selection of the
measuring sensor
Continuous temperature sensor KTY
“Linear” temperature sensor in the motor winding (standard for Lenze motors MDXKX, MDXQA and
MDXMA)
Temperature sensor PTC
PTC thermistor with defined tripping temperature (acc. to DIN 44081 and DIN 44082)
Thermal contact TKO
Thermostat/normally closed contact
Other monitoring KTY, PTC and TKO do not offer full protection. In order to improve the monitoring, Lenze recommends the use of a
bimetal relay.
Alternative monitoring Usecomparators(CMP1...CMP4)todefinethemaximally permitted motor current (blocking c urrent) at low
speeds or when the motor is at standstill. The period of the blocking current can be limited by using a
downstream timing element (TRANS1, TRANS2).
This function can be implemented by interconnecting the corresponding function blocks.
Reactions Depending on the type of temperature monitoring, different reactions can be caused. ( 9-221)
Connection of Lenze motors
Motors MDXKX, MDXQA and MDXMA Motors with thermal contact
Connection Resolver input X7: Pin X7/8 = +, Pin X7/9 =
Encoder input X8: Pin X8/8 = +, Pin X8/5 =
Terminals T1/T2 next to the
terminalsU,V,W
Fault messages (MONIT-)OH3 (MONIT-)OH7 (MONIT-)OH8
Possible reactions
When selecting a motor via C0086, the following codes are preset:
P
o
s
s
i
b
l
e
r
e
a
c
t
i
o
n
s
TRIP: C0583 = 0
OFF: C0583 = 3
Warning: C0584 = 2
OFF: C0584 = 3
TRIP: C0585 = 0
Warning: C0585 = 2
OFF: C0585 = 3
Tripping temperature Fixed at 150 °C Adjustable 45°C ... 150°C (C0121) Fixed, (depending on the
PTC/thermal contact):
PTC: With Rϑ > 1600 Ω
Notes Monitoring is active in the Lenze setting.
When resolver (X7) and encoder (X8) are operated together, connect KTY
to X7 or X8 only. Do n ot assign the unused KTY connection.
Further information about connecting a thermal sensor can be found in
the description of the feedback system
Deactivate monitoring via X7 or
X8 under C0583 = 3 and
C0584 = 3.
Connection is made to DIN 44081
(see Fig. 4-13).