Configuration
Basic configurations
8-2
L
EDSVS9332S-D11 EN 3.0
8.2 Basic configurations
Stop!
Pre-defined basic configuration can be loaded via code C0005. When the configuration is changed
via C0005, the assignment of all inputs and outputs is overwritten with the corresponding basic
assignment. If necessary, adapt the function assignment to the wiring.
For adapting the function assignment to a certain wiring or for extending the signal processing, see
Working with function blocks”.
The internal signal processing is adapted to the drive task (e.g. step control or dancer position
control)by selecting a pre-defined basic configuration. The default setting canbe used to e.g. control
the drive speed.
z A detailed description of the basic configurations with terminal assignments, signal flow
diagrams, and application examples can be found in chapter Application examples”.
z Before loading a basic configuration via C0005, the controller must be inhibited.
Basic configurations already saved can be selected and activated via code C0005. The selection is
made via a four-digit number, each digit being assigned to certain properties.
First digit
Defines the basic function of the configuration.
Configuration C0005 Basic function
1xxx Speed control
4xxx Torque control with speed limitation
5xxx Master for digital frequency coupling
6xxx Slave to digital frequency bus
7xxx Slave to digital frequency cascade