During operation
Operating notes
6-4
L
EDSVS9332S-C EN 3.0
6.2 Information on operation
When operating the controller, please observe the following notes:
Stop!
z Cyclic connection and disconnection of the controller supply voltage at L1, L2, L3 or +U
G
,
-U
G
may overload the internal input current limitation:
Allow at least 3 minutes between disconnection and reconnection.
z During mains switching (L1,L2,L3) it is not important whether further controllers are supplied
via the DC bus.
6.2.1 Switching on the motor side
z Switching on the motor side of the inverter is permissible for emergency switch-off.
z Please note:
Switching while a controller is enabled may cause the fault message OCx”
(short-circuit/earth fault in operating mode x).
For long motor cables and operation of controllers with smaller output power, leakage
currents through interfering cable capacitances may cause the fault message OCx.
Switching equipment on the motor side must be dimensioned for DC voltages
(U
DC max
= 800 V).