Parameter setting
Parameter setting using the keypad
7-10
l
EDSVS9332S-D11 EN 3.0
7.2.8 Diagnostics
In the Diagnostic menu you will find in 2 submenus all codes for
z Drive monitoring
z Fault diagnostics
The operating level displays additional status messages. If several messages are active, the
message with the highest priority is displayed:
Priority Display Meaning
1 GLOBAL DRIVE INIT Initialisation or communication fault between keypad and controller
2 XXX - TRIP Active TRIP (contents of C0168/1)
3 XXX - MESSAGE Active message (contents of C0168/1)
4
Special controller status:
4
Power-up inhibit
5
Source for controller inhibit (at the same time value of C0004 is displayed):
5
STP1 Terminal X5/28
STP3 Keypad or LECOM A/B/LI
STP4 InterBus-S or Profibus
STP5 System bus (CAN)
STP6 C0040
6
Source for quick stop:
6
QSP-term-Ext Input MCTRL-QSP at function block MCTRL is applied to HIGH signal
QSP-C0135 Operating module or LECOM A/B/LI
QSP-AIF INTERBUS-S or PROFIBUS-DP
QSP-CAN System bus (CAN)
7 XXX - WARNING Active warning (contents of C0168/1)
8 xxxx Value under C0004