Function library
Monitorings
9.3.1 Reactions
9-219
L
EDSVS9332S-D11 EN 3.0
9.3 Monitoring
Various monitoring functions protect the drive from impermissible operating conditions.
If a monitoring function is activated,
z a reaction to protect the drive will be activated (configuration ( 9-220)).
z a digital output is set if it is assigned to the corresponding reaction.
z the fault message is entered at the first position in the history buffer. ( 10-4)
9.3.1 Reactions
According to the interferences one or several of the following reactions are possible via the
monitoring function:
Reaction Effects on drive or controller Danger notes
TRIP
(highest priority)
Switches the power outputs U, V, W to a high resistance until TRIP is
reset
The drive is idling (no control!).
After TRIP reset the drive accelerates to its setpoint along the set ramps.
( 10-10)
Message
Switches the power outputs U, V, W to a high resistance as long as the
message is active.
Short-time
message
0.5 s
The drive is idling (no control!) as long as the message is
active
If the message is removed, the drive accelerates to its
setpoint with maximum torque.
The drive restarts automatically if the
message is removed.
Long-term
message
>0.5s
The drive is idling (because of internal controller inhibit!)
as long as the message is active.
If necessary, restart positioning program.
Warning Only display of the operating fault
The drive operates under control.
Off No reaction to operating faults! Monitoring is deactivated.
Since these reactions have no effect on the
drive behaviour, the drive may be destroyed.