Function library
Function blocks
9.2.23 Dead band (DB)
9-91
L
EDSVS9332S-D11 EN 3.0
9.2.23 Dead band (DB)
Purpose
The dead band element is used to set interfering influences around zero, e.g. interferences on analog
input voltages, to digital zero.
D B 1
D B 1 - O U T
D B 1 - I N
C 0 6 2 3
C 0 6 2 2
± 1 9 9 , 9 9 %
C 0 6 2 1
C 0 6 2 0
Fig. 9-55 Dead band element (DB1)
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
DB1-IN a C0623 dec [%] C0622 1 1000 -
DB1-OUT a - - - - - limited to ±199,99 %
Function
z The dead band is parameterised under C0621.
z The gain is set under C0620.
C0621
C0620
DB1 --IN
DB1--OUT
Fig. 9-56 Dead band and gain