Technical data
3.4 Fuses and cable cross-sections
3-7
L
EDSVS9332S-B EN 3.0
3.4 Fuses and cable cross-sections
Type
Mains input L1, L2, L3, PE/motor connection U , V, W Input +UG, -UG
Operation without mains filter Operation with mains filter
Fuse E.l.c.b. Cable
cross-section
2)
Fuse E.l.c.b. Cable
cross-section
2)
Fuse Cable
cross-section
2)
VDE UL VDE mm
2
AWG VDE UL VDE mm
2
AWG mm
2
AWG
9321 M6A 5A B6A
C6A
3)
1 17 M6A 5A B6A
C6A
3)
1 17 6A 1 18
9322 M6A 5A B6A
C6A
3)
1 17 M6A 5A B6A
C6A
3)
1 17 6A 1 18
9323 M10A 10 A B10A 1.5 15 M10A 10 A B10A 1.5 15 12 A 1.5 14
9324 - - - - - M10A 10 A B10A 1.5 15 12 A 1.5 14
9325 M32A 25 A B32A 6 9 M20A 20 A B20A 4 11 20 A 4 12
9326 - - - - - M32A 25 A B32A 6 9 40 A 10 8
9327 M63A 63 A - 16 6 35 A 35 A - 10 7 80 A 25 3
9328 - - - - - 50 A 50 A - 16 5 80 A 25 3
9329 - - - - - 80 A 80 A - 25 3 100 A 50 1
9330 - - - - - 100 A 100 A - 50 0 2 * 80A
1)
2*25 2*3
9331 - - - - - 125 A 125 A - 70 2/0 2 * 100A
1)
2*50 2*1
9332 - - - - - 160 A 175 A - 95 3/0 3 * 80A
1)
3*25 3*3
1)
The DC bus fuses are connected in parallel
2)
The valid local regulations must be observed
3)
Use circuit breakers with tripping characteristic C with short-time mains interruptions or low-inductance mains.
For operation of the controllers in a UL-approved plant:
z Use only UL-approved fuses and fuse holders:
– 500 V to 600 V in the mains input (AC).
– 700 V in the DC bus.
– The tripping characteristic is defined by ”H” or ”K5”.
z Use only UL-approved cables.
Tip!
UL-approved fuses and fuse holders can be obtained from, e.g. Bussmann or Ferraz.
Connection of the motor cables
z The protection of the motor cables is not necessary for functional reasons.
z Refer to the data listed in the table ”Operation with mains filters”.