Configuration
Basic configurations
8.2.3 Master frequency coupling
8-20
L
EDSVS9332S-D11 EN 3.0
Features
The features describe the basic properties of this configuration. Some of them, however, can only
be used by reprogramming.
z Resolver feedback is possible only
z Evaluation of the setpoint (cascading factor) is possible with a factor (numerator/denominator)
for the master frequency output (and thus for all following drives)
z Other evaluation of the setpoint is possible with a factor (numerator/denominator) for the
corresponding slave (gearbox adaptation). Can be set via an analog signal source (standard:
code C0032, C0033)
z External torque limitation is possible
z The QSP or CINH function in the individual drive do not influence the setpoint for the cascade.
z Possible interventions for phase trimming and speed correction via
–LECOM,
analog terminal or
one of the signal sources (function blocks).
z Message following error limit reached” can be set via code
z TRIP when reaching the phase controller limit
z Speed limit of slave 0 = C0011
z Phase controller influence can be set and switched off via the digital input
z Homing function is possible via zero track or touch probe
z Synchronising to a setpoint is possible via zero track or touch probe
z Synchronising characteristic can be set via ramp-function generator