Configuration
Basic configurations
8.2.5 Phase synchronism
8-33
L
EDSVS9332S-D11 EN 3.0
Home position offset = 0 (case 3)
The zero pulse has already occurred once during the homing process.
V
t
Reference
switch
Home position offset=0
Zero pulse = home position
Index pulse
Fig. 8-12 Approaching the home position (case 3)
If the zero pulse has already occurred once or the absolute value encoder (e.g. resolver) is used as
actual value encoder, the drive traverses as described in Fig. 8-12 Approaching via the set ramp
to its home position.
Acceleration a nd deceleration time
The deceleration and acceleration time refers to a change of the output value from 0 to 100%
(C0011). The time C0936 to be set can be calculated as follows:
C0011
0
t
I
t
I
C0936 C0936
t
W1
w2
C0936 = t
i
×
C0011
w
2
w
1
Fig. 8-13 Calculation of the acceleration and deceleration time
In this case the time desired for the change lies between w
1
and w
2
.
The calculated time is to be entered into C0936.