Function library
Function blocks
9.2.49 Process controller (PCTRL1)
9-177
L
EDSVS9332S-D11 EN 3.0
9.2.49.2 Ramp function generator
The setpoint PCTRL-SET is led by a ramp generator with linear characteristic. Thus, setpoint
step-changes at the input can be transformed into a ramp.
100%
0
t
ir
t
if
T
ir
T
if
t
RFG--OUT
[%]
w1
w2
T
ir
= t
ir
100%
w2 w1
T
if
= t
if
100%
w2 w1
Fig. 9-130 Acceleration and deceleration times of the ramp generator
z
The ramps can be adjusted separately for acceleration and deceleration.
Acceleration time t
ir
with C0332.
Deceleration time t
if
with C0333.
z PCTRL-INACT = HIGH
The ramp generator is immediately set to zero.
9.2.49.3 Value range of the output signal
z The process controller operates in bipolar mode in the default setting.
The output value is limited to ±100 %.
z The function can be set in unipolar mode under C0337.
The output value is limited to 0 ... +100 %.
9.2.49.4 Evaluation of the output signal
z The output signal can be evaluated after the limitation block via PCTRL-INFLU.
The process controller can be used or suppressed with this evaluation.
The calcuation is done according to the following formula:
100 % (PCTRL-OUT) = 100 % * 100 % (PCTRL-INFLU).
9.2.49.5 Deactivation of the process controller
z PCTRL-INACT = HIGH deactivates the process controller
PCTRL-OUT is set to zero.
The I-component is set to zero.
The ramp generator is set to zero.