Installation
Electrical installation
4.2.11 Control connections
4-43
L
EDSVS9332S-B EN 3.0
Terminal assignment
Signal type Function
Bold print = Lenze setting (C0005 = 1000)
Level Technical data
X5/28
Digital inputs
Controller inhibit (CINH) HIGH = Start
LOW: 0 … +3 V
X5/E1
Freely assignable
Cancel CW rotation / QSP
HIGH
HIGH: +12 … +30 V
X5/E2 Freely assignable
Cancel CCW rotation / QSP
HIGH
Input current for +24V:
8 mA per input
X5/E3 Freely assignable
Activate JOG setpoint 1
HIGH
Reading and processing of the
X5/E4 Freely assignable
Set error message TRIP
LOW
inpu
s:
Once per ms (average value)
X5/E5 Freely assignable
Reset error message TRIP
LOW-HIGH edge
X5/A1
Digital outputs
Freely assignable
Error message TRIP exists
LOW
LOW: 0 … +3 V
HIGH: +12 … +30 V
X5/A2 Freely assignable
Switching threshold Q
min
: Actual speed (n
act
)<Setpoint
speed (n
x
) in C0017
LOW
Load capacity:
Max. 50 mA per output
X5/A3 Freely assignable
Ready for operation
HIGH
(ex
e
nal
esis
ance a
leas
480 Ω
at +24 V)
X5/A4 Freely assignable
Maximum current I
max
reached
HIGH
Updating of the outputs:
Once per ms
X5/39 – GND2, reference potential for digital signals – Isolated to wards GND1
X5/59 – DC supply for backup operation of the controller in case of
mains failure
+24 V external Current demand: Min. 1 A